Power Module
The Power Module family is a group of modular products for the control of lighting loads. This document describes the following products:
• Model Number: LQSE-4S10-D - Power Module unit for Switching only
• Model Number: LQSE-4T10-D - Power Module unit for 0-10 V/Switching
Features
• Includes QS link for seamless connection to a HomeWorksR QS system.
• Power Module units can be used in a HomeWorksR QS system to control and manage light in an entire home or building.
Power
• 230 V 50/60 Hz
• Lightning strike protection meets ANSI/IEEE standard 62.31-1980. Can withstand voltage surges of up to 6 000 V and current surges of up to 3 000 A.
• Current draw: 50 mA max
• Standby power : 1 W
• BTUs/hour when fully loaded: 4
Output Zone Ratings
• Each zone is rated at 10 AX for switching. Rated for resistive, capacitive, or inductive lighting loads as defined by IEC/EN 60669-2-1.
• Switched outputs utilize latching relays to maintain relay state if control power is lost.
• 0-10 V rated for 50 mA maximum output, source or sink per zone.
Terminals
• Mains wiring: 0,5 mm2 to 6,0 mm2
• 0-10 V Wiring: 0,5 mm2 to 2,5 mm2
• CCI Wiring: 0,5 mm2 to 6,0 mm2
• Zone wiring: 0,5 mm2 to 6,0 mm2
Mounting
• Use an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail
• Width = 9 modules (161,7 mm)
Programming and Compatibility Requirements
• LQSE-4T10-D and LQSE-4S10-D can only be used with the HomeWorksR QS system.
• Setup and programming of the DALIR Power Module is done through the HomeWorksR QS programming software.
• HomeWorks® QS software version 3,0 or higher required.
QS Link Limits
• A QS link in a HomeWorksR QS system can have up to 512 zones (outputs) and 100 devices.
• Each Power Module counts as one device toward the 100 device limit.
Manual Mode Operation
• Zone buttons: — selects zone to control
• Raise/Lower buttons: — turns loads on and off — dim loads up and down (LQSE-4T10-D only)
0-10 V Wiring
(LQSE-4T10-D only)
• 0-10 V zones 1-4 are double-insulated from all other inputs and outputs.
• 0-10 V zones 1-4 are not insulated from each other. They share the same common (negative “–” terminal).