QSE-CI-DMX Control Interface
The QSE-CI-DMX performs different functions depending on the system in which it is operating. The DMX channels (maximum of 32) are mapped to HomeWorks ® QS zones and can be programmed as 1-channel lighting, 1-channel integration, or 3-channel RGB/CMY.
The QSE-CI-DMX can be used to map any HomeWorks ® QS zone to any single DMX512 channel. The QSE-CI-DMX can also be used to simultaneously map any HomeWorks® QS zone to three DMX512 channels for RGB/CMY color-control. The QSE-CI-DMX has an integral RGB/CMY lookup table that maps HomeWorks® QS zone intensities to RGB/ CMY values (colors). The RGB/CMY lookup table can be customized by using the HomeWorks® QS programming software.
In a HomeWorks® QS system, only 32 DMX channels can be programmed per device. The 32 channels can be any of the 512 available addresses. DMX combiners can be used if more than 32 DMX channels need to be controlled from a single DMX universe. If the QSE-CI-DMX is part of a HomeWorks® QS system, GRAFIK Eye® QS zones cannot be programmed to control DMX channels.
Power
24 V =60 mA Typical Power Consumption 1.2 W; 2 Power Draw Units (PDUs) Test conditions: Status lights normal operation, DMX link connected, device powered at 24 V
Communications
Connects to QS-wired device link on HomeWorks® QS processor
Link Capacities
QSE-CI-DMX counts as one device toward link maximum of 100 devices.
Dimensions
4.26 in (108.2 mm) x 5.26 in (133.6 mm) x 1.06 in (26.9 mm)
QS Link Wiring
• Wire the QSE-CI-DMX Interface to the IEC PELV/NEC® Class 2 QS link using the MUX terminal.
• The QS-wired communications link is limited to 100 devices and 512 switch legs (each DMX channel =1 switch leg); 32 DMX channels per QSE?CI?DMX control interface.\
• Wiring may be daisy-chain, star, or T-tap configuration.
• Total length of wire on a QS link must not exceed 2000 ft (610 m).
DMX512 Link Wiring
• Connect the DMX link terminals on the QSE-CI-DMX interface to input terminals on DMX512-controlled equipment.
• Each terminal on the QSE-CI-DMX accepts two 18 AWG (1.0 mm2) wires.
• Link must be 1000 ft (305 m) or less.
• Link must begin and end with link terminators (Lutron® part number LT-1).
• Three pins on the DMX connector for connecting the QSE?CI?DMX to DMX512?controlled equipment.