Adaptive Power Module
The Adaptive Power Module family is a group of modular products for the control of lighting loads. This product is compatible with Lutron HomeWorks QS systems only. This document describes the following product:
• LQSE-4A1-D – 4 zone power module for phase control dimming.
Features
• Leading-edge or trailing-edge dimming for incandescent/ halogen, electronic / magnetic low-voltage, and neon / cold cathode light sources.
• Controls dimmable CFL/LED loads.
• RTISS Equipped® technology compensates for incoming line-voltage variations (up to ± 2% change in frequency/ second) such as changes in RMS voltage, frequency shifts, harmonics and line noise.
• Integral protection for temporary over-current and over-voltage conditions.
• SSL7 compliant for compatibility with Solid State Lighting.
• Includes QS link for seamless connection to a HomeWorks® QS system.
• LEDs on module provide diagnostic information.
• Buttons on module provide load override control.
• Manual Override Contact Closure Input (CCI).
• Power failure memory
Regulatory Approvals
• 120–240 V~ 50/60 Hz - UL® Listed - cUL® Listed - NOM Certified
• 220–240 V~ 50/60 Hz - IEC/EN 60669
Power
• 120–240 V~ 50/60 Hz (cULus and NOM)
• 220–240 V~ 50/60 Hz (IEC/EN 60669)
• Single input feed
• 4 A maximum total input current
• Lightning strike protection meets ANSI/IEEE standard C62.41 and IEC 61000-4-5. Can withstand voltage surges of up to 6 000 V~ and current surges of up to 3 000 A.
• ESD protected above agency requirements per IEC 60669-2-1
Environment
• For thermal specifications, see Output Zone Rating and Mounting section
• Relative humidity: less than 90% non-condensing
• For indoor use only Terminals
• Mains wiring: 1.0 mm? to 2.5 mm? (18 AWG to 12 AWG) (single wire, solid or stranded)
• CCI wiring: 0.5 mm? to 2.5 mm? (22 AWG to 12 AWG) (single wire, solid or stranded)
• Zone wiring: 1.0 mm? to 2.5 mm? (18 AWG to 12 AWG) (single wire, solid or stranded)
• QS Link: 0.5 mm? to 2.5 mm? (22 AWG to 12 AWG) (single wire, solid or stranded)
Manual Mode Operation
• By default, each zone is set to Auto Detect non-dim load type.
• Zone buttons on the unit can be used to: – turn loads on and off. – dim loads up and down when configured to a dimmed load type.
Output Zone Ratings
• No Derating is required if all the conditions below are met:
– Calibration point maximum is 70 ?C (158 ?F). – Room ambient temperature is between 0 ?C and 30 ?C (32 ?F and 86 ?F).
– Panel ambient temperature, within 20 mm (0.80 in) of unit, is between 0 ?C and 50 ?C (32 ?F and 122 ?F).
• 25 W (@120 V~)/50 W (@240 V~): Derating on all zones is required for a single module in a nonventilated enclosure if the room ambient temperature is between 30 ?C and 40 ?C (86 ?F and 104 ?F).
• 50 W (@120 V~)/100 W (@240 V~): Derating on all zones is required in a multiple row non-ventilated enclosure if the temperature is between 30 ?C and 40 ?C (86 ?F and 104 ?F).
• Each zone has a 5 W (incandescent) minimum load requirement.
• Does not support non-dimmable loads
• Automatically selects leading-edge or trailing-edge dimming when configured to "Auto-detect". It can also be configured for a specific load type.
• One load type per zone.
• This module is designed to control loads with ratings as noted in the table below. Outputs cannot be used to control general purpose receptacles.
Mounting
• Mount in IP20 (minimum) rated consumer panel or breaker panel with integrated DIN rail.
• For United States and Canada, use NEMA Type 1 minimum rated enclosure.
• Unit is 9 DIN modules (161.7 mm [6.37 in]) wide.
Нет вопросов о данном товаре, станьте первым и задайте свой вопрос.